Current- and Voltage Transformer
Typical Applications:Expanding precision power measuring ranges of ZES ZIMMER® LMG series
- Current Clamps
- Rogowski Clamps
- Precision Transformer
- Hall Current Transducer
- High Frequency Sensors
- External Shunts
| Sensor (Order No.) | Lower Corner Freq. | Upper Corner Freq. | Precision | Current Range | Primary Connection | LMG95/LMG95e | LMG450 | LMG500 | Typical Applications |
| Current Clamps | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| LMG-Z327 | 45Hz | 10kHz | 1% | 100A | Clamp On | x |
- |
x |
General Purpose |
| LMG-Z326 | 40Hz | 10kHz | 0.8% | 200A | x |
- |
x |
General Purpose | |
| LMG-Z325 | 40 Hz | 5kHz | 2% | 200A | x |
- |
x |
General Purpose | |
| LMG-Z322 | 30Hz | 10kHz | 0.5% | 1000A | x |
x |
x |
General Purpose | |
| LMG-Z329 | 45Hz | 5kHz | 0.5% | 3000A | x |
x |
x |
General Purpose | |
| LMG-Z406/-Z407 | 5Hz | 50kHz | 0.2% | 40A | x |
x |
x |
Frequency Inverter Output | |
| L45-Z06/-Z07 | 5Hz | 50kHz | 0.2% | 40A | x |
x |
x |
Frequency Inverter Output | |
| L45-Z10/-Z11 | 2Hz | 40kHz | 0.15% | 1000A | x |
x |
x |
Frequency Inverter Output | |
| L45-Z16/-Z17 | 5Hz | 10kHz | 0.15% | 3000A | x |
x |
x |
Frequency Inverter Output | |
| L45-Z26 | DC | 2kHz | 1.6% | 1000A | x |
x |
x |
DC-Clamp | |
| Rogowski Clamps | |||||||||
| L45-Z32-Flex500 | 10Hz | 5kHz | 6.1% | 500A | Clamp On | x |
x |
x |
50Hz Power Quality, for difficult to access Areas |
| L45-Z32-Flex1000 | 10Hz | 5kHz | 3.1% | 1000A | x |
x |
x |
||
| L45-Z32-Flex3000 | 10Hz | 5kHz | 3.1% | 3000A | x |
x |
x |
||
| Precision Transformer | |||||||||
| LMG-Z502 | 15Hz | 5kHz | 0.02% | 1500A | Feed Through | x |
x |
x |
50 Hz Applications, High Precision |
| LMG-Z505 | 15Hz | 5kHz | 0.05% | 1500A | x |
x |
x |
||
| LMG-Z510 | 15Hz | 5kHz | 0.1% | 1500A | x |
x |
x |
||
| LMG-Z520 | 15Hz | 5kHz | 0.2% | 1500A | x |
x |
x |
||
| LMG-Z542 | 15Hz | 5kHz | 0.02% | 4000A | x |
x |
x |
||
| LMG-Z545 | 15Hz | 5kHz | 0.05% | 4000A | x |
x |
x |
||
| LMG-Z550 | 15Hz | 5kHz | 0.1% | 4000A | x |
x |
x |
||
| LMG-Z562 | 15Hz | 5kHz | 0.02% | 10kA | x |
x |
x |
||
| LMG-Z570 | 15Hz | 5kHz | 0.1% | 10kA | x |
x |
x |
||
| LMG-Z582 | 15Hz | 5kHz | 0.02% | 10kA | x |
x |
x |
||
| LMG-Z590 | 15Hz | 5kHz | 0.1% | 10kA | x |
x |
x |
||
| Hall Current Transducer | |||||||||
| L45-Z28-Hall50 | DC | 200kHz | 0.9% | 50A | Feed Through | x |
x |
x |
Frequency Inverter Output, Frequency Inverter DC Link, Low Cost |
| L45-Z28-Hall100 | DC | 200kHz | 0.7% | 100A | x |
x |
x |
||
| L45-Z28-Hall200 | DC | 100kHz | 0.65% | 200A | x |
x |
x |
||
| L45-Z29-Hall300 | DC | 100kHz | 0.4% | 300A | x |
x |
- |
||
| L45-Z29-Hall500 | DC | 100kHz | 0.8% | 500A | x |
x |
- |
||
| L45-Z29-Hall1000 | DC | 150kHz | 0.4% | 1000A | x |
x |
- |
||
| L45-Z29-Hall2000 | DC | 100kHz | 0.3% | 2000A | x |
x |
- |
||
| L50-Z29-Hall300 | DC | 100kHz | 0.4% | 300A | - |
- |
x |
||
| L50-Z29-Hall500 | DC | 100kHz | 0.8% | 500A | - |
- |
x |
||
| L50-Z29-Hall1000 | DC | 150kHz | 0.4% | 1000A | - |
- |
x |
||
| L50-Z29-Hall2000 | DC | 100kHz | 0.3% | 2000A | - |
- |
x |
||
| High Frequency Sensors | |||||||||
| L95-Z06 / L95-Z06HV | 5kHz | 500kHz | 0.5% | 15A | 4mm sockets / wire | x |
- |
x |
Summing Current Transducer, Lighting Applications, Ultrasonic |
| LMG-Z601 | 30Hz | 1MHz | 0.25% | 100A | Feed Through | x |
(x) |
x |
Very High Frequency Applications, Avionics, Ultrasonic |
| External Shunts, Low Current | |||||||||
| L95-SHxxx | DC | 100kHz | 0.15% | selectable uA-1A |
4mm sockets | x |
- |
x |
Very Low Current |
| L95-SHxxxP | DC | 10kHz | 0.15% 0.3% |
selectable uA-0.5A |
x |
- |
x |
50Hz Standby Current, Overload Protection 20A | |